Porduct No. |
MFFE007-FM200 |
Main Technical Parameters |
Standard |
Q/HF123-2007 |
System performance |
fixed£¬total flooding type£¬fire extinguishing agent injection time ¡Ü10S |
Operation mode |
Pneumatic remote control operation or manual mechanical£¨Operating Force¡Ü98N£© |
Environmental condition |
ambient temperature |
-10¡æ-50¡æ |
relative temperature |
93¡À3% |
Power supply |
main power source |
AC220V 50Hz |
Auxiliary power supply |
DC24V 3A |
Storage device performance |
|
Storage container volume(L) |
40¡¢70¡¢90¡¢100¡¢120¡¢150¡¢180 |
Fire extinguishing agent filling rate(kg/m3) |
¡Ü1120 |
storage pressure(20¡æ) |
4.2MPa |
MWP(maximum working pressure)(50¡æ) |
6.7MPa |
start method |
remote operation & manual mechanical |
Remote control release station performance |
|
Storage container volume(L)
| 4 |
storage pressure £¨20¡æ£© |
6.0MPa |
Pneumatic time-delay device |
delay time 20S-40S |
start method |
manual mechanical |
Pneumatic cast valve performance |
|
Nominal pressure£¨mm£© |
25¡¢32¡¢40¡¢50¡¢65¡¢80¡¢100¡¢125¡¢150 |
Working pressure£¨MPa£© |
10.0MPa |
Start method |
remote operation & manual mechanical |
additional function |
Equipped with stroke switch, provide a normally open and a normally closed contacts |
The agent would extinguish following fire |
|
electric fire |
liquid fire or melting solid fire |
solid surface fire |
gas fire that the gas would be elimilated before fire extinguishing |
Mairne fire extinguishing system could be placed in the shipping engine room,pump cabin, hold,oil cabin,generate electricity room,paint room,woodworker room, kitchen and so on. |